Chapter 2: Technical Datasheets, Application Matrix and Quality Testing
Updated: 22 min readBy the Azl technical team
Contents
Chapter one of the encyclopedia covers the physics of heat and moisture transfer and advanced materials. This chapter moves from theory to the document engineers and buyers actually rely on: the technical data sheet (TDS). The aim is threefold: to understand what the numbers mean and how to read them, to have a corrected reference table for eight materials common in insulation and protection projects, and to link material choice to facility type and then verify workmanship through documented tests.
How to Read a Technical Datasheet Like an Engineer
The most common mistake when comparing bids is placing two numbers from two different data sheets side by side without asking: Which standard was this measured to? Under what conditions? Is it an average or a minimum? A datasheet number is not an absolute property of the material; it is the result of a specific test on a specific specimen. Four elements govern the meaning of any figure.
1. The test standard: a number without a standard means nothing
Every property should carry the code of the standard used to measure it, such as ASTM C518 for thermal conductivity or ASTM D1621 for compressive strength. Different standards for the same property can give results that are not directly comparable. A clear example: ASTM D412 for tension testing of rubber and elastomers states that its Methods A and B «do not produce identical results», and ASTM E96 for water vapour transmission states that the desiccant and water methods are not directly comparable. So when comparing two materials, first confirm that the standard and the sub-method are the same.
2. Typical values versus guaranteed minimums
Data sheets usually quote «typical values»: laboratory averages that are not a contractual commitment. Some data sheets state explicitly that values are «based on system processing under laboratory conditions» and that field results may vary. By contrast, material specifications such as ASTM C578 for polystyrene set a minimum for each type (for example minimum density and minimum compressive strength). When writing a project specification, ask for the minimum or a range with its tolerance (such as 3000 ± 200 psi) rather than a single typical value.
3. Conditioning and test conditions
Polymer properties are sensitive to temperature, humidity and loading rate. ASTM D638 for tensile testing of plastics stresses that tensile properties «vary with specimen preparation and with speed and environment of testing». Likewise, ASTM D2842 determines water absorption of rigid cellular plastics by immersion under a 5.1 cm head of water for 96 hours, so a data sheet quoting absorption after 24 hours is measuring something different. Always read the footnote giving temperature, specimen age and curing time (for example «7 days at +23 °C»).
4. Initial versus aged thermal conductivity
In closed-cell foams such as polyurethane, thermal resistance drops over time as the blowing agent in the cells gradually exchanges with air. Good data sheets therefore quote an aged value, for example «R-value at 180 days per ASTM C518», with a note that the value «will vary with age and use conditions». Design must use the aged value, not the initial value measured just after production.
R = d / k , k = 0.1442 / R(IP per inch)R is thermal resistance (m²·K/W), d thickness in metres, k thermal conductivity (W/m·K). Converting from imperial units: R-7 per inch corresponds to k ≈ 0.1442 ÷ 7 ≈ 0.021 W/m·K, and R-5 per inch to k ≈ 0.029 W/m·K. Example: a 50 mm XPS board with k = 0.029 gives R ≈ 1.72 m²·K/W.
5. Questions a datasheet must answer before approval
Datasheet review checklist
- Is every property paired with its test standard code and edition or sub-method?
- Are the values typical or minimums? Is the tolerance stated?
- Are conditioning details given: temperature, humidity, specimen age, curing time?
- Is thermal conductivity aged or initial? At what mean temperature was it measured?
- Are service temperature limits separated for dry and wet exposure?
- Is the fire classification tied to a clear standard (EN 13501-1 or ASTM E84) and to the installed system rather than the raw material?
- Is this the latest edition? (issue date and version number in the header)
- Are there separate certificates for special uses: food contact or potable water?
Printable checklist — use your browser's print command.
Master Reference Table for the Eight Materials
The table below brings together typical ranges for eight materials from sources we opened and checked. Where a circulating value was inaccurate we corrected it, and where a property does not apply we entered «—». Note that each range spans several products; any single product has one value in its own data sheet.
| Material | k (W/m·K) | Density (kg/m³) | Tensile or compressive strength | Elongation or hardness | Water absorption / vapour permeance | Service temperature | Fire behaviour |
|---|---|---|---|---|---|---|---|
| Pure polyurea (spray) | — (not a thermal insulant) | ≈ 1,040–1,120 | Tensile 15–21 MPa (D412/D638) | Elongation 350–450%, Shore D 40–55 | Absorption below 1%; permeance about 4.3 g/m²·day (E96) | Dry: −40/−29 to +121 °C; wet range much narrower | Combustible organic material; per product declaration |
| Closed-cell spray polyurethane foam | 0.021–0.022 aged (R 6.7–7 per inch) | ≈ 32–45 (2.0–2.8 lb/ft³) | Compressive ≈ 250–400 kPa (D1621) | Closed cells above 90% (D6226/D2856) | Absorption ≈ 0.9% (D2842); about 63 ng/Pa·s·m² at 25 mm | Up to about +82 °C | Combustible; requires a thermal barrier per code |
| Extruded polystyrene (XPS) | ≈ 0.029 (R-5 per inch at 24 °C) | Minimum 21–48 by type (C578) | Compressive 104–690 kPa by type | — | Max 0.3% by volume (C578/C272); 63–86 ng/Pa·s·m² | Up to about +74 °C | Combustible; needs protection |
| Stone wool (boards/blankets) | 0.035–0.040 (at 15–50 °C) | 40–175 by product | Roof boards 30–80 kPa at 10% (EN 826) | — | Short-term ≤ 0.5–1 kg/m² (EN ISO 29767) | Up to 660 °C for a typical industrial product; melts above 1000 °C | A1 non-combustible (EN 13501-1) |
| Aerogel blanket | 0.014–0.020 (at about 0–25 °C) | 150–200 | — | — | Hydrophobic, per product | Up to 200 °C (building products) or 650 °C (industrial products) | Typical building product C-s1,d0 |
| Floor epoxy with food-contact certification | — | ≈ 1,370–1,400 for unfilled mixed resin | Adhesion ≥ 1.5 MPa with concrete failure (ISO 4624) | Shore D ≈ 76–80 | — | Permanent dry exposure up to +50 °C; higher for short periods | Per system declaration |
| Borated polyethylene | ≈ 0.4 (not a thermal insulant) | ≈ 920–1,280 depending on boron loading | Tensile ≈ 20 MPa | Shore D ≈ 63–66 | Below 0.1% | Up to +80 °C continuous | Combustible |
| Lead (sheet) | — | ≈ 11,340 | Ultimate tensile 12–17 MPa | Yield ≈ 5.5 MPa | — | Melts at 327 °C | Non-combustible |
The second table links each property to its governing standard. Use it when reviewing a data sheet or writing a specification: if a data sheet quotes a property under a different standard, ask why and whether the values can be compared.
| Property | Standard | What it measures | Reader's note |
|---|---|---|---|
| Thermal conductivity | ASTM C518 | Steady-state heat transmission with a heat flow meter apparatus | Secondary comparative method calibrated with specimens measured by C177 |
| Thermal conductivity (reference) | ASTM C177 | Guarded hot plate, an absolute method | Not suitable for specimens with thermal bridges in the heat-flow direction |
| Apparent density | ASTM D1622 | Overall density (with skins) or core density (skins removed) | For spray foam, ask: core or overall density? |
| Compressive strength | ASTM D1621 | Load-deformation curve of rigid cellular plastics | Stone wool is usually tested to EN 826 at 10% deformation |
| Tensile and elongation (elastomers) | ASTM D412 | Tension of rubber and thermoplastic elastomers | Methods A and B do not give identical results |
| Tensile (plastics) | ASTM D638 | Tension of plastics using dumbbell specimens | Sensitive to test speed and environment |
| Hardness | ASTM D2240 | Indentation depth with a Shore A or D durometer | No simple relationship between A and D readings |
| Water vapour transmission | ASTM E96 | Vapour transmission rate by desiccant or water method | Results of the two methods are not comparable |
| Water absorption (rigid foams) | ASTM D2842 | Change in buoyancy after 96 h immersion under 5.1 cm of water | Equivalent to ISO 2896 |
| Water absorption (core materials) | ASTM C272 | Absorption of sandwich core materials by immersion or humidity | Used in XPS data sheets complying with ASTM C578 |
| Open-cell content | ASTM D6226 | Open-cell volume; the rest is closed cells and cell walls | Cutting the specimen can open closed cells and raise the result |
| Reaction to fire | EN 13501-1 | European classes A1 to F with smoke and droplet ratings | Classification applies to the product as installed, not the raw material alone |
Material Profiles: Composition, Application and Cautions
Each material below has a short profile that complements the table: what it is made of, how it is applied and what ruins it on site. For full details see the material page in the materials guide where one exists.
Pure polyurea
Composition: the reaction product of an isocyanate component with an amine blend, curing within seconds into a continuous, flexible, seamless membrane. Application: sprayed with heated high-pressure plural-component equipment at a 1:1 ratio; data sheets state hose and block temperatures (for example 60–70 °C). Cautions: the fast reaction does not forgive poor surface preparation; moisture in concrete causes blistering and delamination, so a suitable primer and moisture testing are required. Wet service limits are far narrower than dry ones (one data sheet gives 4–49 °C wet versus −40 to +121 °C dry). Aromatic grades discolour under UV and need a topcoat. More detail on the polyurea page in the materials guide.
Spray polyurethane foam
Composition: a rigid closed-cell foam formed by reacting a polyol and an isocyanate with a blowing agent; it expands in place and bonds to the substrate. Application: sprayed in successive passes with a maximum thickness per pass set by the data sheet, then covered with a protective layer; roofing foam is usually classified to ASTM C1029 Type III, which requires a minimum compressive strength of 40 psi (about 276 kPa). Cautions: exposed foam degrades quickly in sunlight, and design must use the aged conductivity. It is combustible and needs a thermal barrier or protective coating per code. See the polyurethane foam profile.
Extruded polystyrene (XPS)
Composition: extruded polystyrene with a uniform closed-cell structure and a smooth skin. Application: boards laid over the waterproofing in inverted roofs, under slabs and against foundation walls. Choose the grade by load: ASTM C578 defines types from 104 to 690 kPa. Cautions: the maximum service temperature is about 74 °C, so it must not sit under exposed dark layers or near heat sources. It is attacked by organic solvents found in some adhesives and solvent-borne bituminous coatings, so check chemical compatibility. It is combustible and needs protection.
Stone wool
Composition: mineral fibres spun from molten volcanic rock with a binder, an open structure that lets vapour pass. Application: high-density boards for roofs and facades, and blankets and rolls for pipework and industrial equipment. Cautions: its thermal resistance falls if it gets wet, so it needs protection from water and a vapour barrier on the warm side where required. Compressive strength of roof boards is relatively low (30–80 kPa at 10%) compared with rigid foams, so it is unsuitable under concentrated traffic loads without a load-spreading layer. Its great advantage is the A1 non-combustible classification. See the stone wool page.
Aerogel blankets
Composition: nanoporous silica carried in a fibre batting, trapping air in pores smaller than the mean free path of its molecules. Application: wrapped around pipes and equipment, or used as thin layers to treat thermal bridges where space is limited. Cautions: cost per square metre is high, and cutting releases dust that calls for protective equipment. Temperature limits differ radically between building products (about 200 °C) and industrial products (up to 650 °C), and conductivity rises with temperature (industrial example: 0.020 at 0 °C versus 0.046 at 400 °C).
Floor epoxy with hygiene certification
Composition: a two-component epoxy resin with an amine hardener, applied as a coating, self-levelling screed or sand-filled mortar. Application: on mechanically prepared, dry concrete, with a primer, then body coat and topcoat. Cautions: «food grade» is not a physical property but a certificate: look for a specific conformity certificate (examples in data sheets: an ISEGA certificate for food contact on Sikafloor-264, and BS 6920 conformity for potable-water contact on Sikagard-62). Permanent dry service temperature is only about 50 °C, so steam cleaning or boiling-water washdown may need another system such as polyurethane cement. System details are on the epoxy page.
Borated polyethylene
Composition: polyethylene loaded with boron compounds; the hydrogen in the polymer slows neutrons and the boron absorbs them. Common boron contents are 1–5% by weight, with grades up to 30% for special applications. Application: sheets cut and mechanically fixed in rooms needing neutron shielding, within a design prepared by a specialist. Cautions: it is neither a thermal nor a waterproofing material, its continuous service temperature is about 80 °C, and it is combustible. Using it is a radiation-design decision, not an insulation contractor's decision.
Lead sheet
Composition: a very dense metal (about 11,340 kg/m³) with low tensile strength (12–17 MPa) and a yield stress of about 5.5 MPa, meaning it creeps and sags under its own weight. Application: sheets bonded to gypsum or timber boards or built into doors and frames, with overlaps at joints. Cautions: lead is toxic; cutting, sanding and soldering require occupational health controls. Because it is weak it must be supported by a backing layer, never hung free. Lead thickness is set by radiation shielding calculations, not by the contractor.
Facility Specification Matrix
A good material in the wrong place fails. The matrix below links facility type to the governing requirement, candidate materials and common failure points, followed by detail for each category.
| Facility | Governing requirement | Candidate materials | Common failure point |
|---|---|---|---|
| Residential and commercial roofs | Watertightness + thermal resistance + falls to drains | Bituminous membranes or liquid membranes + XPS or spray foam | Ponding from inadequate falls; wet thermal insulation |
| Basements and buried tanks | Groundwater pressure or soil moisture | Positive-side membranes; crystalline products on the negative side | Choosing the wrong application side |
| Chillers and freezer stores | Continuous vapour barrier + no thermal bridges + frost heave prevention | XPS or PIR floor insulation, sandwich panels, spray foam | Condensation and ice within the insulation; floor heave |
| Metal (shinko) roofs | Thermal movement + fastener joints + sunlight | Spray foam + UV-resistant topcoat, or sandwich panels | Leaks at fasteners and laps; degradation of exposed foam |
| Medical facilities and cleanrooms | Smooth seamless surfaces + disinfectant resistance | Certified epoxy or polyurethane floors | Cracking at joints; damage from untested disinfectants |
| Diagnostic X-ray rooms | Lead equivalence calculated by a specialist | Lead or equivalent boards per the design | Gaps at doors, services and joints |
Residential and commercial buildings: roofs
In a conventional roof the thermal insulation sits below the waterproofing membrane, so the membrane is directly exposed to heat, UV and the large daily temperature swings of Saudi Arabia. In an inverted roof the membrane is laid directly on the slab and topped with low-absorption closed-cell XPS boards, then a separating geotextile that keeps fines out of the joints, then gravel or pavers. The advantage of the inverted roof is that the membrane is protected from heat, UV and mechanical damage. In both cases the falls must be formed with a screed to falls towards the drains before insulating, because standing water accelerates the ageing of any membrane. For practical detail see bituminous membranes and acrylic roof coatings.
Residential and commercial buildings: basements and tanking
Basement tanking means wrapping the buried structure in a continuous waterproofing layer. Positive-side application (the soil and water side) is preferred because water pressure pushes the membrane against the concrete. Negative-side application (from inside) is used for remediation when excavation is not possible, and suits materials that work within the concrete pores, such as crystalline waterproofing, or cementitious systems designed to resist negative pressure. In new buildings with confined excavations retained by shoring walls, pre-applied membranes are fixed before the concrete is poured and bond to it as it cures.
Industrial facilities and cold stores (−25 to −40 °C)
- Vapour barrier on the warm side: vapour pressure in hot, humid outdoor air is much higher than inside a freezer room, so vapour drives inward. The vapour barrier goes on the warm, outer side of the insulation, and any breach lets vapour condense and freeze within the insulation, progressively destroying its thermal value.
- Avoid thermal bridges: columns, beams and metal fasteners penetrating the insulation become points of condensation and ice. They must be thermally broken or wrapped over a sufficient length, and wall-to-floor and wall-to-roof junctions need special care.
- Floor insulation: use boards of high compressive strength such as XPS or PIR, choosing the grade for racking and forklift loads, with a load-spreading concrete slab above.
- Prevent frost heave: long-term cooling of the ground below a store can freeze its water to considerable depth, lifting and cracking the floor. The three recognised measures are non-frost-susceptible fill, insulation that limits the advance of the freezing front, and heating the ground below the building with heater mats or ventilated floors with air ducts.
Metal (shinko) roofs and warehouses
Metal sheeting heats up quickly in the sun and expands and contracts daily, and leaks usually start at fasteners and laps. The first solution is spray polyurethane foam over the sheeting, because it bonds to the corrugated profile and seals fasteners and laps in one continuous layer, provided it is covered with a UV-resistant topcoat (acrylic, aliphatic polyurea or silicone per the data sheet), since exposed foam degrades. The second solution for new buildings is factory-insulated sandwich panels, with close attention to joint and edge details. In both cases verify the soundness and fixing of the sheeting before insulating.
Medical facilities and cleanrooms
ISO 14644-1 classifies cleanrooms into nine classes (ISO Class 1 to ISO Class 9) by the concentration of airborne particles from 0.1 to 5 micrometres. The classification concerns the air, but it imposes practical requirements on surfaces and floors: they must be smooth and seamless so they do not trap dust, floor-to-wall junctions should be coved, and they must withstand the disinfectants used in the facility. Self-levelling epoxy flooring and polyurethane systems are the usual choice.
X-ray rooms: the lead-equivalence concept only
The ability of a wall or door to attenuate X-rays is expressed as lead equivalence: the thickness of lead giving the same attenuation at a given radiation energy. A concrete wall or composite board can therefore achieve a given equivalence without containing lead of that thickness. The decisive factor in execution is continuity: any gap at board joints, around doors or at electrical penetrations defeats the shielding whatever its thickness.
QA/QC Testing Protocols on Site and in the Laboratory
The data sheet proves how the material performs in the laboratory; site tests prove that the installation achieved that performance. The table below summarises the main tests and their standards. Acceptance criteria (the numerical pass limits) are mostly not set by these standards themselves but by the project specification or the manufacturer's data sheet, and must be agreed in writing before work starts.
| Test | Standard | Substrate or application | What to know |
|---|---|---|---|
| Thermal conductivity | ASTM C518 / ASTM C177 | Samples of the delivered material | Laboratory test; requested for supply approval or when conformity is in doubt |
| Pull-off adhesion on metals | ASTM D4541 | Coatings on metal substrates | Protocol 1 measures maximum force; Protocol 2 is a pass/fail test at a set load |
| Pull-off adhesion on concrete | ASTM D7234 | Coatings on concrete | The standard sets no acceptance limit; epoxy data sheets typically state ≥ 1.5 MPa with failure in the concrete |
| Holiday detection on concrete | ASTM D4787 | Non-conductive linings on concrete | High-voltage spark tester, pulsed or continuous DC; for new linings only |
| Holiday detection on metals | ASTM D5162 | Non-conductive coatings on metals | Low-voltage wet sponge up to 0.5 mm, high-voltage spark above that |
| Flood testing | ASTM D5957 | Horizontal waterproofing (parking and plaza decks) | Water head not exceeding 100 mm and no testing in the first 24 h after installation; the guide excludes roof systems |
| Water vapour transmission | ASTM E96 | Membranes, coatings and insulants | State the method (desiccant or water) because results are not comparable |
| Dry film thickness on steel | ASTM D7091 + SSPC-PA 2 | Non-magnetic coatings on ferrous metals | D7091 covers the gauge and verification, SSPC-PA 2 the number of readings by area |
| Dry film thickness on concrete | ASTM D6132 | Coatings on concrete, wood and other substrates | Non-destructive ultrasonic gauge from 8 µm to 7.6 mm; not for soft, deformable coatings |
A practical QC sequence
- 1
Before supply
Review the data sheet against the checklist above, request conformity certificates and batch numbers, and agree acceptance criteria for each test in writing.
- 2
Surface preparation
Record concrete moisture, cleanliness and profile before any coating, because most adhesion failures start from an unprepared surface. Suitable equipment is covered in the academy equipment guide.
- 3
During application
Log surface and air temperature and dew point, measure wet film thickness regularly, and keep samples from each batch.
- 4
After curing
Measure dry film thickness using the method suited to the substrate, then holiday-test linings, then carry out pull-off tests at agreed locations and repair them afterwards.
- 5
Final performance test
Flood test horizontal surfaces where the specification requires it, and document results with photos and dates in a handover file kept with the project records.
If you have a project that needs data sheets reviewed or a test plan prepared, you can request an inspection or send your question to an engineer using the form below.
Frequently asked questions
Why does the k-value of the same material differ between two data sheets?
Because the value depends on the test standard, the mean temperature and the specimen age. Polyurethane foam, for example, is sometimes quoted with an initial value and sometimes with an aged value after 180 days, and stone wool conductivity is given at 15, 20 or 50 °C. Compare only values measured to the same standard at the same temperature, and design with the aged value.
Does higher density mean better thermal insulation?
Not necessarily. Density relates mainly to compressive strength and stiffness, while thermal conductivity is governed by cell structure and the gas inside the cells. XPS types, for example, range from 104 to 690 kPa in compressive strength while their thermal resistance per inch is similar. Choose density for the mechanical load, and choose thickness for the required thermal resistance.
What is the difference between ASTM D4541 and ASTM D7234 for adhesion testing?
Both measure the perpendicular tensile force needed to pull off a dolly bonded to the coating. D4541 is for coatings on metal substrates and D7234 for coatings on concrete. Neither sets an acceptance limit; that comes from the project specification or the manufacturer, and on concrete a failure within the concrete itself at about 1.5 MPa is a common indicator of good adhesion.
Can polyurea be used as thermal insulation?
No. Polyurea is a dense membrane with a density close to that of water, and its role is waterproofing and mechanical and chemical protection, not thermal insulation. When both functions are needed, a combined system is used: polyurethane foam for thermal insulation, then a polyurea layer or topcoat for protection against water and UV, with compatibility between the layers confirmed in the data sheets.
What makes a floor epoxy suitable for food factories?
Not the trade name but the documents: a food-contact or potable-water conformity certificate issued for that specific product, a chemical resistance chart for the cleaning agents in use, and service temperature limits that suit the washdown method. Many epoxy systems tolerate permanent dry heat only up to about 50 °C, so hot-water or steam washdown calls for a different system.
Can an insulation contractor install lead lining in an X-ray room?
Only to an approved design prepared by a qualified radiation protection expert, specifying the lead equivalence of every wall, door and window, with the facility subject to the requirements and licensing of the Nuclear and Radiological Regulatory Commission. The installer is responsible for complete continuity of the layer at joints and penetrations, and for documenting the work for the post-installation radiation survey.
Ask an engineer about your case
Write your question about this topic, and an Azl specialist will reply during working hours.
Nothing is stored on this website; your message opens in WhatsApp for you to send to 0544027180. Privacy policy
References and sources
- ASTM C518-21 Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus — ASTM International · store.astm.org
- ASTM D4541-22 Pull-Off Strength of Coatings Using Portable Adhesion Testers — ASTM International · store.astm.org
- ASTM D7234-19 Pull-Off Adhesion Strength of Coatings on Concrete — ASTM International · store.astm.org
- ASTM D4787-13 Continuity Verification of Liquid or Sheet Linings Applied to Concrete Substrates — ASTM International · store.astm.org
- ASTM D5957 Standard Guide for Flood Testing Horizontal Waterproofing Installations — ASTM International · store.astm.org
- ASTM D7091-22 Nondestructive Measurement of Dry Film Thickness — ASTM International · store.astm.org
- ISO 14644-1:2015 Cleanrooms — Classification of air cleanliness by particle concentration — ISO · iso.org
- ASTM C578 Types and Physical Properties for FOAMULAR XPS (Technical Bulletin) — Owens Corning · dcpd6wotaa0mb.cloudfront.net
- JM Corbond III Closed-Cell Spray Polyurethane Foam Data Sheet — Johns Manville · jm.com
- POLYEURO 5502 Pure Polyurea Technical Data Sheet — Polycoat Products · polycoatusa.com
- Roofrock and Hardrock Technical Datasheet — ROCKWOOL · rockwool.com
- Sikafloor-264 Product Data Sheet — Sika · industry.sika.com
External links pass through Azl's Consumer Safety Center for checking before leading to other organisations' websites. Citing them does not imply they endorse Azl. Technical values are typical and vary by product; the final reference is the approved product's datasheet and the project design. Editorial policy