Azl logo — azl.com.sa
Technical reference

Building Restoration: Treating Honeycombing and Concrete Cracks

Updated: 23 min readBy the Azl technical team

Restoring an old stone wall with temporary shoring and crack injection
Restoring an old stone wall with temporary shoring and crack injection — Illustrative image

Reinforced concrete is durable, but it is not eternal. A small placement defect at the base of a column, a hairline crack in a ceiling or a rust stain on the face of a beam can all look cosmetic, yet some of them are early signs of a problem that affects the safety of the building. This guide explains, in clear engineering terms, how to tell these conditions apart, which materials suit each one, how restoration work is carried out step by step, and when everything must stop until a structural engineer has the final word.

Concrete pathology: honeycombing, cracks, spalling and rebar corrosion

Before discussing any material or repair method, the defect must be diagnosed accurately. The rule stated in ACI 224.1R, the American guide on the causes, evaluation and repair of cracks, is simple and decisive: unless the cause of cracking has been corrected, new cracks will probably form near the original one. Any restoration therefore starts with the question «why did this happen?» and not «what do we fill it with?».

Honeycombing: a placement defect, not a design defect

Honeycombing refers to areas of hardened concrete where the coarse aggregate is exposed with voids between the particles, because the mortar (cement and sand) did not fill the spaces between them. It usually appears at the base of columns, on the underside of beams, at formwork joints and in zones congested with reinforcement. The good news is that honeycombing is usually a local workmanship defect that can be repaired; the bad news is that it can run deeper than it looks on the surface.

  • Poor compaction and vibration: no mechanical vibrator, or vibration that is too short or too widely spaced, leaves air pockets and aggregate that is not coated with mortar.
  • Grout leakage from the formwork: The Concrete Society identifies leakage of the grout or mortar fraction through formwork or construction joints as a main cause of honeycombing; the preventive measure is to seal joints so they are leak-free.
  • Mix deficiencies: insufficient fine material due to incorrect aggregate grading or poor mixing, the other cause the Society names.
  • Congested reinforcement: closely spaced bars at joints and in columns block the coarse aggregate and the vibrator, especially with a stiff mix.
  • Dropping concrete from a height: free-falling concrete inside a narrow column separates the aggregate from the mortar and lets it collect at the bottom.

Why does honeycombing matter? Surface honeycombing looks cosmetic, but deeper honeycombing reduces the concrete cover that protects the steel, opening a direct path for moisture, chlorides and carbon dioxide to reach the reinforcement, a durability risk The Concrete Society also highlights. If the honeycombing is in a column or at a bearing zone, it reduces the effective load-carrying section, and it turns from a workmanship defect into a structural matter that needs an engineer's opinion before any breaking out.

Crack classification: non-structural and structural

Not every crack is dangerous, and not every hairline crack is harmless. The distinction depends on the crack's orientation, location, pattern and timing, and on whether it is active (widening or moving) or dormant. ACI 224.1R describes the common non-structural cracks as follows: plastic shrinkage cracks form when surface water evaporates faster than bleed water rises, creating tensile stresses in concrete that is still plastic and weak. Drying shrinkage cracks result from moisture loss from the cement paste while that shrinkage is restrained by the aggregate and adjoining elements. Thermal cracks result from temperature differences within the element or between it and its surroundings.

Typical crack patterns and their preliminary meaning
Crack typeUsual shape and orientationWhen it appearsPreliminary classification
Plastic shrinkageShort parallel or map cracks on slab surfaces, usually shallowWithin the first hours after placingUsually non-structural
Drying shrinkageRegularly spaced cracks in long slabs and walls, or fine map crackingWeeks to months after placingUsually non-structural, but opens a path for moisture
ThermalCracks perpendicular to the restrained movement, on exposed roofs and long wallsWith daily and seasonal temperature cyclesUsually non-structural, and may be active (breathing)
FlexuralVertical cracks in the tension zone: bottom of beam or slab at midspan, or top over supportsAfter loading or increased loadsStructural: needs an engineer
ShearDiagonal cracks at roughly 45° near supports and columnsAfter loadingStructural and serious: needs an engineer urgently
Settlement or differential settlementDiagonal cracks from the corners of doors and windows, or stepped cracks in blockwork, wider at top or bottomGradually, and may accelerate after water leaks into the soilStructural/geotechnical: structural engineer and soil investigation
Reinforcement corrosionLongitudinal cracks following the bar line, often with rust stains and spallingAfter years in serviceDurability damage that becomes structural if the steel loses section
This table is only a preliminary triage aid. A single crack can have more than one cause, and the final classification belongs to a structural engineer after inspection.

Spalling and reinforcement corrosion

Steel inside concrete is chemically protected: the cement paste is highly alkaline (pH around 13), and this environment forms a passive protective layer on the steel surface. That layer is lost mainly through carbonation or chlorides, after which the following deterioration chain begins:

  • Carbonation: carbon dioxide from the air reacts with the alkaline compounds of the cement and converts them to calcium carbonate, lowering alkalinity progressively from the surface inward. The Concrete Society notes that loss of passivity occurs at about pH 11. Once the carbonation front reaches the steel, it can corrode in the presence of moisture and oxygen.
  • Chloride ingress: chloride salts from sea air, saline groundwater or contaminated aggregate break down the passive layer locally and cause dangerous pitting corrosion, which eats into the bar section at a specific point. Repair guidance based on EN 1504 places the risk at concentrations above about 0.2–0.4%.
  • Rust expansion: corrosion products occupy a larger volume than the original steel, pressing on the cover from inside until it cracks longitudinally, delaminates and falls off (spalling), exposing the steel and accelerating deterioration.
  • Cover failure: cover thinner than required, porous concrete or honeycombing near the bars all shorten the time carbonation or chlorides need to reach the reinforcement.

Saudi conditions: why concrete deteriorates faster here

Environmental deterioration factors by region
RegionDominant factorEffect on concreteWhat it means for repair
Coastal cities: Jeddah, Dammam, Khobar, JubailAirborne marine chlorides and high humidityAccelerated rebar corrosion and cover spalling in beams, balconies and tanksRemove chloride-contaminated concrete, not just visible damage; rebar protection, corrosion inhibitors and a final protective coating
Eastern Province: sabkha groundSabkha soils and shallow groundwater rich in chlorides and sulfatesSulfate attack on foundations and column necks, and rebar corrosion through capillary riseDeal with the moisture source and insulate foundations; assess under SBC 303 and SBC 304
Riyadh and inland regionsHigh heat, dry air and windRapid plastic shrinkage, drying shrinkage and thermal stresses on exposed roofsSchedule work in cooler hours, cure rigorously, and use materials within their application temperature limits
The Saudi concrete code SBC 304 includes durability requirements for sulfate and chloride exposure classes and explicitly addresses sabkha exposure. Geotechnical behavior of soils, foundations and settlement is governed by SBC 303. For more detail see the Saudi Building Code guide.

In hot regions in particular, the application temperature range in each product's data sheet must be respected. For example, the data sheet for the epoxy injection resin Sikadur-52 Injection specifies an injection temperature range of +5 to +30 °C and notes that pot life shortens as temperature rises. In practice, injecting a crack in an exposed roof slab at midday in a Riyadh summer can cause the injection to fail before the crack is filled.

Tool: is this crack dangerous?

Answer a few short questions about the crack's location, orientation and width and whether it is widening over time, and you will get a preliminary classification to help you set the priority and decide whether you need a structural engineer before taking any other step.

Tool: is this crack dangerous?

Enter what you see. The result is preliminary guidance, not a structural judgement.

Accompanying signs

Monitor and surface treatment

Most likely non-structural (shrinkage or thermal). Mark both ends with a pencil, date it and photograph monthly; if stable, treat the surface or seal with a flexible coating, and if it widens, re-run this tool.

Non-binding guidance. Cracks in load-bearing members and settlement must be assessed and their repair designed by a licensed structural engineer.

Repair materials matrix and standards

A common mistake in quotations is to describe materials by brand names or site slang instead of technical descriptions. A phrase such as «acrylic or Sika cylinders» is inaccurate: what is technically meant is a polymer-modified cementitious repair mortar, or a latex bonding agent of the acrylic or SBR (styrene-butadiene rubber) type added to the mix or brushed onto the surface. «Sika» is a manufacturer's brand, not a material. A good contract names the material type, its class and the standard it complies with, and attaches its data sheet. See how to read technical data sheets to compare offers objectively.

Concrete repair materials matrix
MaterialComposition and key propertiesBest useGoverning standard
Non-shrink cementitious groutPackaged dry blend of hydraulic cement and other ingredients, mixed with water only; flowable, designed to avoid loss of height after placementFilling deep honeycombing by pouring into formwork, equipment bases, voids under bearing platesASTM C1107 (external source via the Consumer Safety Center)
Polymer-modified repair mortarCement and fine aggregate with a polymer (acrylic or SBR) that improves adhesion, reduces permeability and allows vertical and overhead application. Classified in Europe as R1 to R4, with R3 and R4 for structural repairRepairing spalls, shallow and medium honeycombing, and restoring cover around reinforcementEN 1504-3 (class R4: compressive strength of at least 45 MPa and bond of at least 2.0 MPa)
Latex bonding agentLatex emulsion applied by brush, broom or spray to bond fresh concrete or mortar to hardened concreteBond coat before repair mortar where the data sheet requires itASTM C1059 (external source via the Consumer Safety Center) (specific to latex bonding agents)
Epoxy injection and bonding resinsLow-viscosity two-component system with high tensile and compressive strength that re-bonds the crack faces. The American standard classifies these systems into seven types (I–VII) by properties, three grades (1–3) by viscosity and consistency, and temperature classes (A–F)Injecting dormant cracks that are dry or damp (not saturated) to restore bond; cracks as narrow as 0.05 mm can be injected according to ACI 224.1RASTM C881 (external source via the Consumer Safety Center) and EN 1504-5 (class F: force-transmitting)
Polyurethane injection resinsReact with water; hydrophobic grades form a relatively rigid, low-absorption foam, while hydrophilic grades form a flexible gel or foam that swells with waterStopping water leakage through wet cracks and joints in tanks, basements and tunnels. They do not restore structural strengthEN 1504-5 (class D: ductile, and class S: swelling)
Reinforcement corrosion protectionActive coatings (cementitious or zinc-rich) that restore protection to the steel, barrier coatings (epoxy) that isolate it from water and oxygen, or migrating corrosion inhibitors that diffuse through the concrete to the steelAll steel exposed during restoration after cleaning; migrating inhibitors for chloride-contaminated zones without breaking outEN 1504-7 (reinforcement corrosion protection) and Principle 11 of EN 1504-9
Externally bonded carbon fiber (CFRP)Carbon fiber laminates or fabrics bonded with epoxy to the element surface; very high tensile strength, lightweight and non-corrodingStrengthening beams, columns and slabs to increase capacity or make up a deficiency, only to a structural engineer's designACI 440.2R (external source via the Consumer Safety Center)
Reference correction: some quotations cite ASTM A775 for rebar protection during repair. That standard covers epoxy-coated reinforcing bars coated in the factory and does not cover protective coatings applied on site to existing steel; the appropriate reference is EN 1504-7. All figures above must be checked against the data sheet of the product approved for the project.

Epoxy is not the answer to every crack. Cured epoxy is rigid; if it is injected into an active crack that moves with temperature or load, a new crack may open next to it. The data sheets of some epoxy resins also state that they must not be injected into wet or saturated cracks. In that case polyurethane is used first to stop the water, and the engineer decides whether the crack also needs its strength restored.

Standard execution procedures

The procedures below summarize accepted practice in technical guidance (ICRI 310.1R, EN 1504-10, ACI 224.1R and manufacturers' literature). Exact details such as waiting times, layer thicknesses and moisture conditions are always taken from the data sheet of the approved material and from the engineer's specification. For the full operating version used by crews, see the field SOPs.

A) Honeycomb repair

  1. 1

    Inspect and define the extent

    Sound the area with a hammer to find the limits of hollow concrete and document the dimensions with photos. If the honeycombing is in a column or bearing zone or extends behind the steel, refer it to the engineer before breaking out; temporary propping may be required.

  2. 2

    Mark and cut the edges

    Lay out the repair area in regular shapes and saw-cut the edges to avoid feather edges that later debond. Repair notes based on ICRI 310.1R call for a perimeter saw cut at least 12 mm deep.

  3. 3

    Remove weak concrete

    Break out all loose and hollow concrete down to sound, hard concrete, using hand tools or light electric breakers that do not cause microcracking in the sound concrete.

  4. 4

    Clean and prepare the surface

    Remove dust and loose particles with oil-free compressed air or water, and achieve the surface roughness recommended in the repair mortar's data sheet.

  5. 5

    Pre-wet or prime

    Pre-wet the concrete to a saturated surface-dry condition with no standing water, or apply a primer, as the material's data sheet requires. Do not combine both unless the data sheet says so.

  6. 6

    Bond coat

    Apply the bonding agent (latex to ASTM C1059, epoxy to ASTM C881, or the system's own bond slurry) and place the mortar within its open time, before the bond coat dries.

  7. 7

    Pour or trowel

    For deep and large honeycombing: fix tight formwork and pour non-shrink grout (ASTM C1107) from a top opening while expelling air. For shallow honeycombing: apply polymer-modified repair mortar in layers within the per-layer thickness allowed by the data sheet, compacting well.

  8. 8

    Curing

    Protect the repair from rapid evaporation immediately after finishing using the method the manufacturer recommends (water spray, wet coverings or a curing compound). This is critical in the Saudi summer to prevent shrinkage cracks.

B) Pressure injection of cracks

  1. 1

    Diagnose and decide on injection

    Confirm that the crack is dormant or that the engineer has approved injecting it, and select the material: epoxy to restore bond in dry or damp, non-saturated cracks, or polyurethane to stop water leakage.

  2. 2

    Clean the crack

    Remove dust, oil, paint and efflorescence along the crack and blow it out with clean air. ACI 224.1R lists cleaning the cracks as the first step of injection.

  3. 3

    Install injection ports

    Fix surface ports on the crack, or drill angled holes that intersect the crack for mechanical packers, at a spacing suited to crack depth and member thickness per the engineer's specification and the material data sheet.

  4. 4

    Seal the crack surface

    Seal the crack surface between ports with an epoxy paste, on both faces if the element is exposed on both sides, to stop resin escaping during injection. Let the paste harden.

  5. 5

    Inject from the bottom up

    On vertical and inclined cracks, start at the lowest port and continue until resin appears at the next port, then cap the first port and move to the next, and so on. Monitor pressure and quantity continuously and respect the pot life and injection temperature range in the data sheet.

  6. 6

    Remove the seal and finish

    Once the resin has cured, remove the ports and sealing paste and dress the surface, the final step in the ACI 224.1R sequence.

  7. 7

    Verify quality

    As the engineer requires: take a small core across the injected crack to confirm depth of penetration, or use ultrasonic pulse velocity to ASTM C597, which the standard explicitly lists for evaluating the effectiveness of crack repairs.

C) Columns and beams with corroded reinforcement

  1. 1

    Engineering assessment and temporary propping

    The structural engineer decides the permissible extent of breaking out and whether the element needs temporary shoring before concrete removal, because breaking out around the steel of a loaded column temporarily reduces its section. Repair notes based on ICRI 310.1R require contacting the engineer before removing concrete in columns.

  2. 2

    Break out behind the bars

    Remove deteriorated, chloride-contaminated or carbonated concrete around the corroded bars, with a clearance behind the bar of typically at least 19 mm or 6 mm larger than the largest aggregate in the repair material, whichever is greater, per ICRI 310.1R, continuing along the bar until sound, uncorroded steel is reached.

  3. 3

    Clean the steel

    Remove corrosion products, scale and concrete residue by abrasive blasting or mechanical cleaning to the preparation grade required by the protective coating's data sheet, using the ISO 8501-1 classification of steel surface preparation grades.

  4. 4

    Assess section loss

    Measure the remaining bar diameter at the worst points. If the steel has lost section, work stops and the engineer is informed; only the engineer decides on supplementary bars, their laps and anchorage.

  5. 5

    Anticorrosion coating

    Apply the protective coating (active cementitious, zinc-rich, or epoxy barrier, according to the approved system under EN 1504-7) around the full perimeter of the exposed bar, in the number of coats set by the data sheet, taking care not to contaminate the adjacent concrete with barrier coatings.

  6. 6

    Repair mortar

    Prepare and pre-wet the concrete or apply the bond coat, then rebuild the section with a structural repair mortar (typically class R3 or R4 to EN 1504-3), or pour non-shrink grout into formwork for large sections, achieving the concrete cover specified in the design.

  7. 7

    Curing

    Wet cure or apply a curing compound immediately after finishing, for the period set by the manufacturer, because rapid drying causes shrinkage cracks and debonding at the edges.

  8. 8

    Final protective coating

    In coastal or chloride-contaminated environments, apply a surface protection coating resistant to chloride and carbon dioxide ingress (EN 1504-2); the engineer may also recommend a migrating corrosion inhibitor for adjacent areas that were not broken out.

Quality control checklist before handover

  • A design or written instructions from the engineer for every structural element
  • Condition documented before and after breaking out with photos and measurements
  • Delivered materials match the approved data sheets, batch numbers and expiry dates
  • Air and substrate temperatures recorded at the time of injection or pouring
  • Exposed steel inspected, any section loss documented and reported to the engineer
  • Bond checked by light hammer sounding for hollow areas after curing
  • Verification tests requested by the engineer carried out (cores or ultrasonic pulse velocity)
  • Handover file with materials, locations, photos and maintenance instructions

Printable checklist — use your browser's print command.

Non-destructive testing: the engineer's diagnostic tools

Visual inspection alone is not enough to assess deteriorated concrete. The structural engineer or an accredited testing laboratory uses a set of non-destructive and partially destructive tests, and ACI 228.2R reviews these methods and their limitations. The key rule: never rely on a single test in isolation; read the results together.

Main test methods used to assess existing buildings
TestWhat it measuresWhat it is used forLimitations
Ultrasonic pulse velocity (ASTM C597)Transit time of an ultrasonic wave through the concreteAssessing uniformity and relative quality, detecting internal voids and cracks, and evaluating the effectiveness of crack injectionDoes not measure strength directly; affected by moisture saturation and by reinforcement near the wave path
Covermeter / rebar locator (BS 1881-204, ACI 228.2R)Bar positions and cover depth using electromagnetic methodsVerifying actual cover and locating steel before coring or installing packersAccuracy drops with congested steel or greater depth
Rebound hammer (ASTM C805)Rebound number of the concrete surfaceComparing concrete uniformity between elements and identifying suspect zonesNot a basis for accepting or rejecting concrete; estimates strength only when correlated with cores taken on site; affected by carbonation and moisture
Half-cell potential (ASTM C876)Electrical potential of the steel relative to a reference electrodeMapping the probability of active corrosion and locating break-out zonesGives a probability, not a corrosion rate; needs chloride and carbonation results to interpret
Carbonation depth by phenolphthalein (EN 14630)Phenolphthalein solution sprayed on a fresh fracture or corePink zone is alkaline (pH above about 9), colorless zone is carbonated; depth is compared with coverPartially destructive; requires a fracture or a core
Chloride content (e.g., ASTM C1152 for acid-soluble chloride)Chloride in powdered concrete samples at different depthsDetermining the depth of contamination and the required extent of break-outLaboratory test that needs samples from site
Under ASTM C876, potentials more positive than −200 mV (copper/copper sulfate electrode) are generally interpreted as less than 10% probability of active corrosion, more negative than −350 mV as greater than 90% probability, and values in between as uncertain. These tests are performed by an engineer or accredited laboratory; Azl carries out the repair according to their results and the engineer's design.

Cost: what determines the price?

Concrete restoration is not priced per square meter the way insulation is, because the true quantity is only known after breaking out, and part of it may require structural design. The cost of concrete repair and crack injection is therefore priced after inspection and engineering design, and any figure given before that is a guess that should not be relied on. The main cost drivers are:

  • Diagnosis: is the condition non-structural (shallow honeycombing, shrinkage cracks) or does it require structural assessment, laboratory tests and design?
  • Quantity and depth: total crack length and depth, element thickness, and the volume of concrete actually removed, which is often larger than it appears before breaking out.
  • Steel condition: surface rust only, or section loss requiring supplementary bars.
  • Material type: epoxy or polyurethane resin, structural-class repair mortar, protective coatings and carbon fiber systems vary widely in cost.
  • Access and temporary support: scaffolding, work at height or in tight spaces, and shoring if the engineer requires it.
  • Environment: working in an occupied building, near the sea or inside a tank increases protection and preparation requirements.
  • Permits and supervision: restoration permit fees and engineering office supervision where needed.
  • Post-repair testing: cores and ultrasonic pulse velocity if required for verification.

How to request an assessment of your case

  1. 1

    Send photos via WhatsApp

    Photos of the defect from several angles, with a scale next to the crack, plus a general photo showing where the element is in the building (column, beam, ceiling, wall, tank).

  2. 2

    Preliminary, non-binding guidance

    We review the photos and give you initial direction: does the case look non-structural and ready for an execution inspection, or does it need a structural engineer first? This guidance is not an engineering judgement.

  3. 3

    Site inspection

    A site visit to measure cracks, sound the concrete for hollow areas, check moisture sources and identify the tests required.

  4. 4

    Engineering design where needed

    If the case is structural, a licensed structural engineer prepares the assessment report and the repair or strengthening design, and any required permits are obtained through Balady.

  5. 5

    Execution

    Works are carried out according to the approved design and the materials' data sheets, following the procedures above.

  6. 6

    Quality control and handover

    Verification tests, full photo documentation, maintenance instructions and a written warranty whose duration depends on the type of work and the element's condition, per the warranty policy.

Learn about the scope of the concrete repair and crack treatment service, or request an inspection in your city: concrete restoration in Riyadh, rebar corrosion treatment in Jeddah and building restoration in Dammam. If your question goes beyond a single element, such as choosing between full restoration and rehabilitation, see the building rehabilitation guide.

Common mistakes that make restoration fail

  • Plastering over honeycombing with ordinary cement mortar without breaking out: it covers the void without filling it and usually debonds within months.
  • Painting rust without breaking out behind the steel: the back of the bar stays in contaminated concrete, corrosion returns and the repair spalls.
  • Injecting an active crack with epoxy: a new crack opens next to it because the cause was not treated, exactly as ACI 224.1R warns.
  • Ignoring the water source: repairing a beam or ceiling without stopping a leak from the roof or bathroom brings the problem back, which is why restoration is often paired with waterproofing.
  • Ignoring application temperature and curing: an excellent mortar fails if it is applied to a hot surface and left uncured.
  • Using brand names instead of specifications: a contract that does not state the material type and standard gives you no way to verify what was installed.

Frequently asked questions

Can a column with honeycombing be repaired without demolishing it?

In most cases, yes. If the honeycombing is localized, weak concrete is removed down to sound material and the section is rebuilt with non-shrink grout poured into formwork or with a structural repair mortar. But a column is a load-bearing element, so the structural engineer first decides the extent of breaking out, the need for temporary propping, and whether the remaining section is adequate or needs strengthening. Demolition is considered only if the assessment shows the defect is extensive or the concrete is unfit.

When are cracks in a ceiling or wall dangerous and in need of immediate action?

Immediate action is needed for diagonal cracks near columns and supports, cracks in the columns themselves, cracks accompanied by visible ceiling sag, falling concrete or exposed corroded steel, and cracks that widen quickly or come with sticking doors and windows. In these cases, clear the area of loads and people if in doubt, and request an assessment by a licensed structural engineer before any repair.

What does crack injection or honeycomb repair cost in Saudi Arabia?

There is no fixed price that can be relied on before an inspection, because the cost depends on crack length and depth, the type of resin, the volume of concrete to be removed, the condition of the steel, access difficulty, and whether engineering design or testing is required. These works are therefore priced after inspection and engineering design. Send clear photos with a scale to get a preliminary estimate of the scope.

What is the difference between epoxy and polyurethane crack injection?

Epoxy cures to re-bond the crack faces and restore bond; it is used in dormant cracks that are dry or damp but not saturated, and EN 1504-5 classifies it as force-transmitting. Polyurethane reacts with water to form a foam or flexible gel that stops leakage and suits wet cracks in tanks and basements, but it does not restore structural strength. They may be used together: polyurethane to stop the water, then epoxy if the engineer requires it.

Why do rust and spalling sometimes come back after repair?

Usually because the repair only treated what was visible: concrete behind the steel was not broken out, chloride-contaminated or carbonated concrete was not removed, the steel was not properly cleaned, or the moisture source was ignored. The solution is to define the extent of contamination by testing, break out sufficiently, protect the steel, and add inhibitors or protective coatings as the engineer recommends.

Do I need a municipal permit to restore my building?

The Balady platform offers an «Issuing a Building Restoration Permit» service for returning a building to good condition through technical repairs without adding new components or altering structural elements; it requires a valid building permit and a contract with an engineering office. Whether you need it depends on the scope of work, and works affecting structural elements require an engineering design. Check with an engineering office or the municipality for your specific case.

Send photos of the problem for assessment

Choose the problem and where it is, then attach photos in the WhatsApp chat once it opens. Preliminary advice is non-binding and doesn't replace an inspection.

Nothing is stored on this website; your message opens in WhatsApp for you to send to 0544027180. Privacy policy

References and sources

  1. ACI 224.1R-07: Causes, Evaluation, and Repair of Cracks in Concrete Structures — American Concrete Institute (ACI) · lauwtjunnji.weebly.com
  2. ASTM C881/C881M-20a: Epoxy-Resin-Base Bonding Systems for Concrete — ASTM International · store.astm.org
  3. ASTM C1059/C1059M-21: Latex Agents for Bonding Fresh to Hardened Concrete — ASTM International · store.astm.org
  4. Concrete Repair and Protection in Accordance with EN 1504 — Sika · sika.com
  5. Sikadur-52 Injection Normal: Product Data Sheet — Sika · industry.sika.com
  6. General Concrete Repair Notes (ICRI 310.1R surface preparation) — Euclid Chemical · euclidchemical.com
  7. ACI PRC-440.2-17: Externally Bonded FRP Systems for Strengthening Concrete Structures — American Concrete Institute (ACI) · concrete.org
  8. ACI PRC-228.2-13: Nondestructive Test Methods for Evaluation of Concrete in Structures — American Concrete Institute (ACI) · concrete.org
  9. ASTM C597-22: Ultrasonic Pulse Velocity Through Concrete — ASTM International · store.astm.org
  10. ASTM C876-15: Corrosion Potentials of Uncoated Reinforcing Steel in Concrete — ASTM International · store.astm.org
  11. Carbonation Depth — The Concrete Society · concrete.org.uk
  12. Issuing a Building Restoration Permit — Balady Platform (MOMAH) · balady.gov.sa

External links pass through Azl's Consumer Safety Center for checking before leading to other organisations' websites. Citing them does not imply they endorse Azl. Technical values are typical and vary by product; the final reference is the approved product's datasheet and the project design. Editorial policy